Three-Phase Oil Type Transformer S9, S11

The three-phase oil-immersed distribution transformer produced by our company adopts a new insulation structure to improve the short-circuit resistance; the iron core is made of high-quality cold-rolled silicon steel sheets; high-voltage windings are made of high-quality oxygen-free copper wire as the material , and adopts multi-layer cylindrical structure; all sturdy parts adopt special anti-loosening treatment.

Request a Quote

Description

Reliable Structure

Based on the traditional structure and mature technology, our company has made many improvements, such as:
1) Spiral coil with longitudinal oil passage, better internal heat dissipation;
2) Improved the effective support of the coil end surface, and the ability to resist short-circuit current is stronger;
3) The new hoisting structure and body positioning structure are adopted to ensure more reliable in long-distance transportation and operation;
4) We have many unique and reliable structures to serve you;
5) Selecting a transformer with a higher performance level will have a higher level of technical content.

Excellent Materials

1) Oxygen-free copper wire with lower resistivity is selected, and after a series of additional surface treatments, it is smoother and free of burrs and sharp corners, making the load loss of the transformer lower and the electrical performance more reliable.
2) Select high-quality silicon steel sheets. With the improvement of performance level, use silicon steel sheets with lower unit loss to make the transformer no-load loss lower.
3) Select high-quality laminated wood insulation parts, never crack, even under the action of short-circuit current, the wire will not move.
4) Transformer oil after deep filtration is selected. The lower water, gas and impurity levels make the transformer work more reliable.
5) Select high-quality rubber sealing materials to effectively prevent aging and prevent leakage.
6)  All raw materials have passed the quality inspection, and all raw material manufacturers have undergone strict review in accordance with the national standard ISO9000.

Service Condition

Transformer normal use conditions
The altitude does not exceed 1000m;
Ambient temperature:
Maximum temperature +40℃
The average temperature of the hottest month is +30°C
The highest annual average temperature +20℃
Outdoor minimum temperature -25℃

Transformer special use conditions

The altitude exceeds 1000m;

Ambient temperature:
Maximum temperature +40℃
Minimum temperature -25℃

(Specify when ordering)

Rated capacity

(kVA)

Voltage groupConnection methodImpedance voltage

(%)

(kW) LossNo-load current

(%)

(kg) Weight 

(L×B×H)

Outline dimension

Gauge vertical/

horizontal

HVLVNo-loadLoadMachineoiltotal
511

10.5

10

6.3

6

0.4

0.69

Yyn0

Dyn11

40.070.3545045145550×450×800400/350
100.090.43.57055185550×450×800
200.110.523.011060235660×505×850
300.130.63/0.62.313065265660×530×870450/340
500.170.91/0.872.019580365740×600×930450/380
630.21.09/1.041.923080400720×620×1000
800.251.31/1.251.926095460770×640×1030450/430
1000.291.58/1.51.830095510820×710×970550/450
1250.341.89/1.81.73351155851040×680×1080550/470
1600.42.31/2.21.64051306851090×670×1130550/520
2000.482.73/2.61.54901508101160×760×1090
2500.563.2/3.051.45651709351215×775×1180650/550
3150.673.83/3.651.465520010951345×890×1205
4000.84.52/4.31.384025013851450×935×1240
5000.965.41/5.151.293523515051410×970×1290750/600
6304.51.26.21.1110033018301595×1040×1315850/660
8001.47.51.0136037022251765×1170×1350
10001.710.31.0145547525551855×1255×1490
12501.9612.00.9171554531401885×1270×1590
16002.414.50.8209563036801950×1620×2020850/700
20002.819.80.8234071541902060×1740×2050820/820
25003.323.00.7292083051002250×1800×21001070/1070

Note:tapping range of high-voltage:±5%±2×2.5%;frequency:50HZ

 

Product Features

  • Voltage Conversion and Transmission: The S9 series transformer can convert high voltage into low voltage or increase low voltage to meet the voltage requirements of different power equipment, achieving stable transmission of electrical energy.
  • Energy saving and loss reduction: Compared with the previous S7 series, the S9 series transformers have reduced no-load and load losses, with significant energy-saving effects, which helps to reduce the operating costs of the power system.
  • High reliability: Adopting a highly reliable structural design improves the operational reliability of the product and reduces power outages caused by transformer failures.
  • Strong environmental adaptability: The S9 series transformer can operate stably under various environmental conditions, including high temperature, low temperature, humidity and other harsh environments, adapting to a wide range of load requirements.
  • Easy maintenance: Adopting a fully sealed structure reduces maintenance workload and extends the service life of the transformer.

 

Product images

1 04 1 03 1 02 1 051 061 01